Search Results (806 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2020-7566 1 Schneider-electric 2 Modicon M221, Modicon M221 Firmware 2026-05-29 7.1 High
A CWE-334: Small Space of Random Values vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to break the encryption keys when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller.
CVE-2021-22788 1 Schneider-electric 28 140cpu65150, 140cpu65150 Firmware, 140noc77101 and 25 more 2026-05-29 7.5 High
A CWE-787: Out-of-bounds Write vulnerability exists that could cause denial of service when an attacker sends a specially crafted HTTP request to the web server of the device. Affected Product: Modicon M340 CPUs: BMXP34 (Versions prior to V3.40), Modicon M340 X80 Ethernet Communication Modules: BMXNOE0100 (H), BMXNOE0110 (H), BMXNOC0401, BMXNOR0200H RTU (All Versions), Modicon Premium Processors with integrated Ethernet (Copro): TSXP574634, TSXP575634, TSXP576634 (All Versions), Modicon Quantum Processors with Integrated Ethernet (Copro): 140CPU65xxxxx (All Versions), Modicon Quantum Communication Modules: 140NOE771x1, 140NOC78x00, 140NOC77101 (All Versions), Modicon Premium Communication Modules: TSXETY4103, TSXETY5103 (All Versions)
CVE-2021-22787 1 Schneider-electric 28 140cpu65150, 140cpu65150 Firmware, 140noc77101 and 25 more 2026-05-29 7.5 High
A CWE-20: Improper Input Validation vulnerability exists that could cause denial of service of the device when an attacker sends a specially crafted HTTP request to the web server of the device. Affected Product: Modicon M340 CPUs: BMXP34 (Versions prior to V3.40), Modicon M340 X80 Ethernet Communication Modules: BMXNOE0100 (H), BMXNOE0110 (H), BMXNOC0401, BMXNOR0200H RTU (All Versions), Modicon Premium Processors with integrated Ethernet (Copro): TSXP574634, TSXP575634, TSXP576634 (All Versions), Modicon Quantum Processors with Integrated Ethernet (Copro): 140CPU65xxxxx (All Versions), Modicon Quantum Communication Modules: 140NOE771x1, 140NOC78x00, 140NOC77101 (All Versions), Modicon Premium Communication Modules: TSXETY4103, TSXETY5103 (All Versions)
CVE-2021-22785 1 Schneider-electric 28 140cpu65150, 140cpu65150 Firmware, 140noc77101 and 25 more 2026-05-29 7.5 High
A CWE-200: Information Exposure vulnerability exists that could cause sensitive information of files located in the web root directory to leak when an attacker sends a HTTP request to the web server of the device. Affected Product: Modicon M340 CPUs: BMXP34 (Versions prior to V3.40), Modicon M340 X80 Ethernet Communication Modules: BMXNOE0100 (H), BMXNOE0110 (H), BMXNOC0401, BMXNOR0200H RTU (All Versions), Modicon Premium Processors with integrated Ethernet (Copro): TSXP574634, TSXP575634, TSXP576634 (All Versions), Modicon Quantum Processors with Integrated Ethernet (Copro): 140CPU65xxxxx (All Versions), Modicon Quantum Communication Modules: 140NOE771x1, 140NOC78x00, 140NOC77101 (All Versions), Modicon Premium Communication Modules: TSXETY4103, TSXETY5103 (All Versions)
CVE-2021-22713 1 Schneider-electric 21 Ion7650 Firmware, Powerlogic Ion7300, Powerlogic Ion7300 Firmware and 18 more 2026-05-29 7.5 High
A CWE-119:Improper restriction of operations within the bounds of a memory buffer vulnerability exists in PowerLogic ION8650, ION8800, ION7650, ION7700/73xx, and ION83xx/84xx/85xx/8600 (see security notifcation for affected versions), which could cause the meter to reboot.
CVE-2018-7795 1 Schneider-electric 2 Powerlogic Pm5560, Powerlogic Pm5560 Firmware 2026-05-29 5.4 Medium
A Cross Protocol Injection vulnerability exists in Schneider Electric's PowerLogic (PM5560 prior to FW version 2.5.4) product. The vulnerability makes the product susceptible to cross site scripting attack on its web browser. User inputs can be manipulated to cause execution of java script code.
CVE-2020-7567 1 Schneider-electric 2 Modicon M221, Modicon M221 Firmware 2026-05-29 7.1 High
A CWE-311: Missing Encryption of Sensitive Data vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to find the password hash when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller and broke the encryption keys.
CVE-2019-10953 5 Abb, Phoenixcontact, Schneider-electric and 2 more 20 Pm554-tp-eth, Pm554-tp-eth Firmware, Ilc 151 Eth and 17 more 2026-05-29 7.5 High
ABB, Phoenix Contact, Schneider Electric, Siemens, WAGO - Programmable Logic Controllers, multiple versions. Researchers have found some controllers are susceptible to a denial-of-service attack due to a flood of network packets.
CVE-2019-6857 1 Schneider-electric 58 140cpu65150, 140cpu65150 Firmware, 140cpu65160 and 55 more 2026-05-29 7.5 High
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Modicon Quantum, Modicon Premium (see security notification for specific versions) which could cause a Denial of Service of the controller when reading specific memory blocks using Modbus TCP.
CVE-2019-6856 1 Schneider-electric 58 140cpu65150, 140cpu65150 Firmware, 140cpu65160 and 55 more 2026-05-29 7.5 High
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Modicon Quantum, Modicon Premium (see security notification for specific versions) which could cause a Denial of Service when writing specific physical memory blocks using Modbus TCP.
CVE-2019-6829 1 Schneider-electric 4 Modicon M340, Modicon M340 Firmware, Modicon M580 and 1 more 2026-05-29 7.5 High
A CWE-248: Uncaught Exception vulnerability exists in Modicon M580 (firmware version prior to V2.90) and Modicon M340 (firmware version prior to V3.10), which could cause a possible denial of service when writing to specific memory addresses in the controller over Modbus.
CVE-2019-6819 1 Schneider-electric 38 Bmeh582040, Bmeh582040c, Bmeh584040 and 35 more 2026-05-29 7.5 High
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists which could cause a possible Denial of Service when specific Modbus frames are sent to the controller in the products: Modicon M340 - firmware versions prior to V3.01, Modicon M580 - firmware versions prior to V2.80, All firmware versions of Modicon Quantum and Modicon Premium.
CVE-2018-7852 1 Schneider-electric 8 Modicon M340, Modicon M340 Firmware, Modicon M580 and 5 more 2026-05-29 7.5 High
A CWE-248: Uncaught Exception vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause denial of service when an invalid private command parameter is sent to the controller over Modbus.
CVE-2018-7821 1 Schneider-electric 3 Modicon M221, Modicon M221 Firmware, Somachine Basic 2026-05-29 7.5 High
An Environment (CWE-2) vulnerability exists in SoMachine Basic, all versions, and Modicon M221(all references, all versions prior to firmware V1.10.0.0) which could cause cycle time impact when flooding the M221 ethernet interface while the Ethernet/IP adapter is activated.
CVE-2020-7568 1 Schneider-electric 2 Modicon M221, Modicon M221 Firmware 2026-05-29 3.1 Low
A CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exists in Modicon M221 (all references, all versions) that could allow non sensitive information disclosure when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller.
CVE-2018-7798 1 Schneider-electric 2 Modicon M221, Somachine Basic 2026-05-29 8.2 High
A Insufficient Verification of Data Authenticity (CWE-345) vulnerability exists in the Modicon M221, all versions, which could cause a change of IPv4 configuration (IP address, mask and gateway) when remotely connected to the device.
CVE-2022-0715 1 Schneider-electric 66 Scl Series 1029 Ups, Scl Series 1029 Ups Firmware, Scl Series 1030 Ups and 63 more 2026-05-29 8.9 High
A CWE-287: Improper Authentication vulnerability exists that could cause an attacker to arbitrarily change the behavior of the UPS when a key is leaked and used to upload malicious firmware. Affected Product: APC Smart-UPS Family: SMT Series (SMT Series ID=18: UPS 09.8 and prior / SMT Series ID=1040: UPS 01.2 and prior / SMT Series ID=1031: UPS 03.1 and prior), SMC Series (SMC Series ID=1005: UPS 14.1 and prior / SMC Series ID=1007: UPS 11.0 and prior / SMC Series ID=1041: UPS 01.1 and prior), SCL Series (SCL Series ID=1030: UPS 02.5 and prior / SCL Series ID=1036: UPS 02.5 and prior), SMX Series (SMX Series ID=20: UPS 10.2 and prior / SMX Series ID=23: UPS 07.0 and prior), SRT Series (SRT Series ID=1010/1019/1025: UPS 08.3 and prior / SRT Series ID=1024: UPS 01.0 and prior / SRT Series ID=1020: UPS 10.4 and prior / SRT Series ID=1021: UPS 12.2 and prior / SRT Series ID=1001/1013: UPS 05.1 and prior / SRT Series ID=1002/1014: UPSa05.2 and prior), APC SmartConnect Family: SMT Series (SMT Series ID=1015: UPS 04.5 and prior), SMC Series (SMC Series ID=1018: UPS 04.2 and prior), SMTL Series (SMTL Series ID=1026: UPS 02.9 and prior), SCL Series (SCL Series ID=1029: UPS 02.5 and prior / SCL Series ID=1030: UPS 02.5 and prior / SCL Series ID=1036: UPS 02.5 and prior / SCL Series ID=1037: UPS 03.1 and prior), SMX Series (SMX Series ID=1031: UPS 03.1 and prior)
CVE-2018-7794 1 Schneider-electric 58 140cpu65150, 140cpu65150 Firmware, 140cpu65160 and 55 more 2026-05-29 7.5 High
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Modicon Quantum, Modicon Premium (see security notification for specific versions) which could cause a Denial of Service when reading data with invalid index using Modbus TCP.
CVE-2018-7792 1 Schneider-electric 2 Modicon M221, Modicon M221 Firmware 2026-05-29 7.5 High
A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to decode the password using rainbow table.
CVE-2021-22792 1 Schneider-electric 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more 2026-05-29 6.5 Medium
A CWE-476: NULL Pointer Dereference vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Unity Pro versions (former name of EcoStruxureª Control Expert, all versions), PLC Simulator for EcoStruxureª Process Expert including all HDCS versions (former name of EcoStruxureª Process Expert, all versions), Modicon Quantum CPU (part numbers 140CPU*, all versions), Modicon Premium CPU (part numbers TSXP5*, all versions).