Search Results (112 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2026-7310 1 Hitachienergy 1 Mach Hidraw 2026-05-27 N/A
A heap-based buffer overflow vulnerability exists in XML parser functionality in the HiDraw. An authenticated malicious user with local access can exploit this vulnerability using a specially crafted XML file which may lead to memory corruption and potential arbitrary code execution. Successful exploitation could result in application crashes (denial of service) and compromise the confidentiality and integrity of the affected system.
CVE-2026-8479 1 Hitachienergy 1 Rtu500 Firmware 2026-05-27 N/A
IEC 60870-5-104 used in bidirectional mode in RTU500 is vulnerable for a NULL pointer dereferencing, if a specially crafted sequence of messages is sent for a certain time, causing Denial of Service impact. Product is only affected if IEC 60870-5-104 functionality in bidirectional mode (BCI) is configured.
CVE-2026-1773 1 Hitachienergy 9 Rtu500 Firmware, Rtu520, Rtu520 Firmware and 6 more 2026-05-26 7.5 High
IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame. Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation.
CVE-2026-2459 1 Hitachienergy 3 Reb500, Reb500 Firmware, Relion Reb500 2026-04-18 8.1 High
A vulnerability exists in REB500 for an authenticated user with Installer role to access and alter the contents of directories that the role is not authorized to do so.
CVE-2026-1772 1 Hitachienergy 9 Rtu500 Firmware, Rtu520, Rtu520 Firmware and 6 more 2026-04-17 5.3 Medium
RTU500 web interface: An unprivileged user can read user management information. The information cannot be accessed via the RTU500 web user interface but requires further tools like browser development utilities to access them without required privileges.
CVE-2026-2460 1 Hitachienergy 3 Reb500, Reb500 Firmware, Relion Reb500 2026-04-16 8.1 High
A vulnerability exists in REB500 for an authenticated user with low-level privileges to access and alter the content of directories by using the DAC protocol that the user is not authorized to do so.
CVE-2024-2617 1 Hitachienergy 1 Rtu500 Firmware 2026-04-15 7.2 High
A vulnerability exists in the RTU500 that allows for authenticated and authorized users to bypass secure update, if secure update feature was not enabled on all CMUs of a RTU500. If a malicious actor successfully exploits this vulnerability, they could use it to update the RTU500 with unsigned firmware.
CVE-2025-10217 1 Hitachienergy 1 Asset Suite 2026-04-15 N/A
A vulnerability exists in Asset Suite for an authenticated user to manipulate the content of performance related log data or to inject crafted data in logfile for potentially carrying out further malicious attacks. Performance logging is typically enabled for troubleshooting purposes while resolving application performance related issues.
CVE-2025-1036 1 Hitachienergy 1 Tropos 2026-04-15 N/A
Command injection vulnerability exists in the “Logging” page of the web-based configuration utility. An authenticated user with low privileged network access for the configuration utility can execute arbitrary commands on the underlying OS to obtain root SSH access to the TropOS 4th Gen device.
CVE-2025-7740 1 Hitachienergy 1 Supros 2026-04-15 N/A
Default credentials vulnerability exists in SuprOS product. If exploited, this could allow an authenticated local attacker to use an admin account created during product deployment.
CVE-2024-2097 1 Hitachienergy 1 Modular Advanced Control For Hvdc 2026-04-15 7 High
An authenticated malicious client can send a special LINQ query to execute arbitrary code remotely (RCE) on the SCM server from List control, and execute the arbitrary code on the same system where SCMArchivedEventViewerTool is installed in the case of SCM Tools.
CVE-2024-9928 1 Hitachienergy 1 Nsd570 Firmware 2026-04-15 5.3 Medium
A vulnerability exists in NSD570 login panel that does not restrict excessive authentication attempts. If exploited, this could cause account takeover and unauthorized access to the system when an attacker conducts brute-force attacks against the equipment login. Note that the system supports only one concurrent session and implements a delay of more than a second between failed login attempts making it difficult to automate the attacks.
CVE-2025-1037 1 Hitachienergy 1 Tropos 2026-04-15 N/A
By making minor configuration changes to the TropOS 4th Gen device, an authenticated user with the ability to run user level shell commands can enable access via secure shell (SSH) to an unrestricted root shell. This is possible through abuse of a particular set of scripts and executables that allow for certain commands to be run as root from an unprivileged context.
CVE-2025-1038 1 Hitachienergy 1 Tropos 2026-04-15 N/A
The “Diagnostics Tools” page of the web-based configuration utility does not properly validate user-controlled input, allowing an authenticated user with high privileges to inject commands into the command shell of the TropOS 4th Gen device. The injected commands can be exploited to execute several set-uid (SUID) applications to ultimately gain root access to the TropOS device.
CVE-2023-5769 1 Hitachienergy 8 Rtu520, Rtu520 Firmware, Rtu530 and 5 more 2026-02-27 5.4 Medium
A vulnerability exists in the webserver that affects the RTU500 series product versions listed below. A malicious actor could perform cross-site scripting on the webserver due to user input being improperly sanitized.
CVE-2025-39205 1 Hitachienergy 1 Microscada X Sys600 2026-01-30 6.5 Medium
A vulnerability exists in the IEC 61850 in MicroSCADA X SYS600 product. The certificate validation of the TLS protocol allows remote Man-in-the-Middle attack due to missing proper validation.
CVE-2025-39201 1 Hitachienergy 1 Microscada X Sys600 2026-01-26 6.1 Medium
A vulnerability exists in MicroSCADA X SYS600 product. If exploited this could allow a local unauthenticated attacker to tamper a system file, making denial of Notify service.
CVE-2025-39202 1 Hitachienergy 1 Microscada X Sys600 2026-01-26 7.3 High
A vulnerability exists in in the Monitor Pro interface of the MicroSCADA X SYS600 product. An authenticated user with low privileges can see and overwrite files causing information leak and data corruption.
CVE-2025-39203 1 Hitachienergy 1 Microscada X Sys600 2026-01-26 6.5 Medium
A vulnerability exists in the IEC 61850 of the MicroSCADA X SYS600 product. An IEC 61850-8 crafted message content from IED or remote system can cause a denial of service resulting in disconnection loop.
CVE-2025-39204 1 Hitachienergy 1 Microscada X Sys600 2026-01-26 6.5 Medium
A vulnerability exists in the Web interface of the MicroSCADA X SYS600 product. The filtering query in the Web interface can be malformed, so returning data can leak unauthorized information to the user.